Technical data
12.2 Technical data, Power Modules
12.2.2

Technical data, PM240-2

12.2.2.1

General data, PM240-2

Feature
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Line impedance
Starting current
Pulse frequency (factory
setting)
Electromagnetic
compatibility
Braking methods
Degree of protection
Operating temperature
Storage temperature
Relative humidity
Dirt and contamination
Environmental requirements Protected against damaging chemical substances according to environmental class 3C2 to
Shock and vibration
Installation altitude
Standards
398
Version
380 V ... 480 V 3-ph. AC ± 10%
0 V 3-ph. AC ... input voltage x 0.95 (max.)
50 ... 60 Hz, ± 3 Hz
0 ... 650 Hz, depending on the control mode
0.7 without line reactor; 0.85 with line reactor
Uk ≥ 1%, a line reactor is required for lower values
Less than the input current
4 kHz
The pulse frequency can be increased in 2 kHz steps. An increase in the pulse frequency
results in a lower output current.
Devices with filters in compliance with EN 61800-3: 2004 are suitable for Category C2
environments. For details, see the Hardware Installation Manual, Appendix A2.
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20 built-in units
PT devices
LO without derating:
HO without derating:
LO/HO with derating:
-40° C ... +70° C (-40° F ... 158° F)
< 95% - condensation not permissible
Protected according to pollution degree 2 to EN 61800-5-1: 2007
EN 60721-3-3; 1995
Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-1:
1997
Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997
Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995
without derating:
up to 1000 m above sea level
with derating:
up to 4000 m above sea level
UL, cUL, CE, C-tick, SEMI F47
The drive only satisfies the UL requirements when UL-certified fuses are used.
IP20 when mounted in a control cabinet
IP54 on the control cabinet wall
0° C ... +40° C
0° C ... +50° C
to 60° C
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB