Setting functions
8.7 Application-specific functions
Parameter
p0583
p0585
p2181
p2192
p2193 = 2
p3230 = 586
p3231
For more information, see the List Manual (the parameter list and function diagram 8013).
298
Description
Maximum probe measuring time (factory setting 10 s)
Maximum measuring time for the probe. If there is no new pulse before the
maximum measuring time elapses, the inverter sets the actual speed value in
r0586 to zero.
The time is restarted with the next pulse.
Probe gear factor (factory setting 1)
The inverter multiplies the measured speed by the gear factor and then displays
it in r0586.
Load monitoring response (factory setting 0)
Response for evaluating load monitoring.
0 Load monitoring disabled
1 A07920 for speed too low
2 A07921 for speed too high
3 A07922 for speed outside tolerance
4 F07923 for speed too low
5 F07924 for speed too high
6 F07925 for speed outside tolerance
Load monitoring delay time (factory setting 10 s)
Delay time for evaluating load monitoring.
Load monitoring configuration (factory setting: 1)
2: Speed deviation and load failure monitoring.
Load monitoring actual speed value (factory setting 0)
Result of the speed calculation with the evaluation of the speed monitoring.
Load monitoring speed deviation (factory setting 150 rpm)
Permissible speed deviation of load monitoring.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB