Siemens SINAMICS G120 Operating Instructions Manual page 89

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

7.
8.
9.
10.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Set the most important parameters to suit your application.
We recommend the
setting "Calculate motor
data only".
Select whether the inverter evaluates one or two encoders.
Select the interface to which the encoder is connected.
Select a standard
encoder from the list
of encoder types.
• Code number
< 1000:
Encoders with
integrated
DRIVE-CLiQ
• 100x: Resolvers
with different
pole pair
numbers
• 2xxx: sin/cos
encoder
• 3xxx: HTL/TTL
encoders and
SSI encoders
If you cannot find your encoder in the list, then initially select the closest
possible encoder type. Continue the configuration, and then adapt the
encoder data. See also Section: Adapting the encoder data (Page 90).
This step is only visible if you have configured the basic positioner.
Select the encoder that you use
for position sensing.
5.4 Basic commissioning with STARTER
Commissioning
89