Siemens SINAMICS G120 Operating Instructions Manual page 125

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Control word 1 (STW1)
Control word 1 (bits 0 ... 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11
... 15 specific to the inverter).
Bit
Significance
Telegram 20
0
0 = OFF1
0 → 1 = ON
1
0 = OFF2
1 = No OFF2
2
0 = Quick stop (OFF3)
1 = No quick stop (OFF3)
3
0 = Inhibit operation
1 = Enable operation
4
0 = Disable RFG
1 = Do not disable RFG
5
0 = Stop RFG
1 = Enable RFG
6
0 = Inhibit setpoint
1 = Enable setpoint
7
0 → 1 = Acknowledge faults
8, 9
Reserved
10
0 = No control via PLC
1 = Control via PLC
11
---
1)
12
Not used
13
---
1)
14
---
1)
15
CDS bit 0
If you change over from another telegram to telegram 20, then the assignment of the previous telegram is kept.
1)
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Explanation
All other
telegrams
The motor brakes with the ramp-down time p1121 of the
ramp-function generator. The inverter switches off the motor
at standstill.
The inverter goes into the "ready" state. If, in addition
bit 3 = 1, then the inverter switches on the motor.
Switch off the motor immediately, the motor then coasts
down to a standstill.
The motor can be switched on (ON command).
Quick stop: The motor brakes with the OFF3 ramp-down
time p1135 down to standstill.
The motor can be switched on (ON command).
Immediately switch-off motor (cancel pulses).
Switch-on motor (pulses can be enabled).
The inverter immediately sets its ramp-function generator
output to 0.
The ramp-function generator can be enabled.
The output of the ramp-function generator stops at the actual
value.
The output of the ramp-function generator follows the
setpoint.
The inverter brakes the motor with the ramp-down time
p1121 of the ramp-function generator.
Motor accelerates with the ramp-up time p1120 to the
setpoint.
Acknowledge fault. If the ON command is still active, the
inverter switches to"closing lockout" state.
Inverter ignores the process data from the fieldbus.
Control via fieldbus, inverter accepts the process data from
the fieldbus.
0 = Direction
Invert setpoint in the inverter.
reversal
1 = MOP up
Increase the setpoint saved in the motorized potentiometer.
1 = MOP down
Reduce the setpoint saved in the motorized potentiometer.
Reserved
Changes over between settings for different operation
interfaces (command data sets).
7.4 PROFIdrive profile for PROFIBUS and PROFINET
Configuring the fieldbus
Signal
interconnection
in the inverter
p0840[0] =
r2090.0
p0844[0] =
r2090.1
p0848[0] =
r2090.2
p0852[0] =
r2090.3
p1140[0] =
r2090.4
p1141[0] =
r2090.5
p1142[0] =
r2090.6
p2103[0] =
r2090.7
p0854[0] =
r2090.10
p1113[0] =
r2090.11
p1035[0] =
r2090.13
p1036[0] =
r2090.14
p0810 =
r2090.15
125