Configuring Communication To The Control - Siemens SINAMICS G120 Operating Instructions Manual

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Configuring the fieldbus
7.2 Communication via PROFINET
7.2.3

Configuring communication to the control

Loading GSDML
In order to establish communication between the inverter and control system via PROFINET,
you need the device file of the inverter "GSDML" for your control. You can then configure the
communication.
Procedure
Proceed as follows to load the GSDML of the inverter:
Load the GSDML of the inverter into the PROFINET-Controller, i.e. into your control system.
You can load the GSDML of your inverter in two ways:
● You can find the GSDML of the SINAMICS inverter on the Internet
(http://support.automation.siemens.com/WW/view/en/22339653/133100).
● The GSDML is saved in the inverter. If you insert the memory card in the inverter and set
p0804 = 12 , the GSDML will be written to the /SIEMENS/SINAMICS/DATA/CFG folder
on the memory card as a compressed file (PNGSD.ZIP).
Unpack the GSDML before you use the device file.
You have loaded the GSDML of the inverter.