Technical data

12.1

Technical data, CU250S-2 Control Unit

Feature
Order numbers
Operating voltage
Current consumption
Power loss
Output voltages
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Data
6SL3246-0BA22-1BA0
6SL3246-0BA22-1PA0
6SL3246-0BA22-1FA0
6SL3246-0BA22-1CA0
You have two options for the Control Unit power supply:
Supply from the Power Module.
The sum of all of the currents of the following interfaces is limited to 0.8 A:
Encoder power supply
Drive-Cliq
Power supply for the operator panel
Analog outputs
24 V output voltage (terminal 9)
24 V PROFIBUS teleservice
Resolver excitation
If a short circuit occurs at the output terminals when the CU is fully loaded, then the
Power Module overcurrent protection response, and the inverter is tripped with
overcurrent (Power Module and Control Unit).
External supply via terminals 31 and 32 with 20.4 ... 28.8 V DC, a maximum of 200
VA.
Use a DVC A power supply with Protective Extra Low Voltage (PELV) according to
EN 61800-5-1, Class 2.
Example: SITOP Power 5 A power supply unit
The 0 V of the power supply must be connected with low resistance to the PE of the
system.
The power supply is electrically isolated from the other terminal strip.
max 0.5 A
12.0 W
+24 V out (terminal 9)
+10 V out (terminal 1)
HTL encoder (terminal 33)
With RS485 interface for the following protocols:
USS
Modbus RTU
With PROFIBUSinterface.
With RJ45 connector for the following fieldbuses:
PROFINET
EtherNet/IP
With CANopen interface.
Plus power loss of the output voltages.
18 V ... 26.8 V (max. 200 mA).
Depending on the operating voltage
9.5 V ... 10.5 V (max. 10 mA)
Operating voltage - 2 V, max. 200 mA
12
385