Siemens SINAMICS G120 Operating Instructions Manual page 93

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Procedure
To initiate motor data identification and optimization of the motor control, proceed as follows:
1. Open by double-clicking on the control panel in
2. Assume master control for the converter.
3. Set the "Enable signals"
4. Switch on the motor.
5. Relinquish the master control after the motor data
6. Click the
You have now completed motor data identification.
Self-optimization of the closed-loop control
If you have also selected a rotating measurement with self-optimization of the speed control
in addition to the motor data identification, then you must switch on the motor again as
described above and wait for the optimization run to be completed.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
STARTER.
The converter starts the motor data identification.
This measurement can take several minutes. After
the measurement, the converter switches off the
motor.
identification.
Save (RAM to ROM) button.
5.4 Basic commissioning with STARTER
Commissioning
93