Setting The Address - Siemens sinamics G120 Operating Instructions Manual

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

Installing
4.8 Connecting the inverter to the fieldbus
4.8.3.5

Setting the address

Valid address range: 1 ... 125
Procedure
To change the bus address, proceed as follows:
1. Set the address using one of the subsequently listed options:
– using the address switch
– from an operator panel using parameter p0918
– in STARTER using screen form "Control Unit/Communication/PROFIBUS" – or using
2. Switch off the inverter supply voltage.
3. Wait until all LEDs on the inverter go dark.
4. Switch on the inverter supply voltage again.
Your settings become active after switching on.
You have now changed the bus address.
114
Overview of the interfaces (Page 85)
the expert list in parameter p0918
After you have changed the address in STARTER, carry out RAM to ROM (
You set the PROFIBUS address of the inverter using
the address switch on the Control Unit, in parameter
p0918 or in STARTER.
In parameter p0918 (factory setting: 126) or in
STARTER, you can only set the address, if all ad-
dress switches are set to "OFF" (0) or "ON" (1).
If you have specified a valid address with the ad-
dress switches, this address will always be the one
that takes effect and parameter p0918 cannot be
changed.
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
).
Converter with CU250S-2 Control Unit