Saving Settings On A Pc - Siemens SINAMICS G120 Operating Instructions Manual

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Backing up data and series commissioning

9.2 Saving settings on a PC

9.2
Saving settings on a PC
Precondition
With the supply voltage switched on, you
can transfer the inverter settings from the
inverter to a PG/PC, or the data from a
PG/PC to the inverter.
This requires you to have installed the
STARTER commissioning tool on your
PG/PC.
You will find additional information about STARTER in Section Tools to commission the
converter (Page 39).
Inverter → PC/PG
Procedure
To back up the settings, proceed as follows:
1. Go online with STARTER :
2. Select the button "Download project to PG":
3. To save the data in the PG, select the button:
4. Go offline with STARTER :
You have backed up the settings.
PC/PG → inverter
The procedure depends on whether you also transfer settings of safety functions or not.
Procedure without safety functions
To load the settings from the PG to the inverter, proceed as follows:
1. Go online with STARTER :
2. Select the button "Download project to target system":
3. To save the data in the inverter so that it is not lost when the power fails, select the "Copy
RAM to ROM" button:
4. Go offline with STARTER :
You have transferred the settings from the PG to the inverter.
332
.
.
.
.
.
.
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
.
.
Converter with the CU250S-2 Control Unit (vector)

Hide quick links: