Communication Via Profibus; What Do You Need For Communication Via Profibus; Connect The Frequency Inverter To Profibus - Siemens SINAMICS G120 Operating Instructions Manual

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Configuring the fieldbus

7.3 Communication via PROFIBUS

7.3
Communication via PROFIBUS
7.3.1

What do you need for communication via PROFIBUS?

Check the communication settings using the following table. If you answer "Yes" to the
questions, you have correctly set the communication settings and can control the inverter via
the fieldbus.
Questions
Is the inverter correctly
connected to the PROFIBUS?
Have you configured the
communication between the
inverter and the higher-level
controller?
Do the addresses in the inverter
and the higher-level controller
match?
Is the same telegram set in the
higher-level controller and in the
inverter?
Are the signals that the inverter
and the controller exchange via
PROFIBUS correctly
interconnected?
7.3.2

Connect the frequency inverter to PROFIBUS

Permissible cable lengths, routing and shielding the PROFIBUS cable
For a data transfer rate of 1 Mbit/s, the maximum permissible cable length is 100 m.
You will find additional information on this topic in the Internet:
● Product support (http://support.automation.siemens.com/WW/view/en/1971286)
● PROFIBUS user organization installation guidelines
(http://www.profibus.com/downloads/installation-guide/)
Recommended PROFIBUS connectors
We recommend connectors with the following order numbers for connecting the PROFIBUS
cable:
● 6GK1500-0FC00
● 6GK1500-0EA02
116
Description
See Section: Connect the frequency
inverter to PROFIBUS (Page 116).
See Section: Configuring communication
to the control (Page 117)
See Section: Setting the address
(Page 118).
Adapt the telegram in the inverter. See
Section: Select telegram – procedure
(Page 118).
Adapt the interconnection of the signals in
the controller to the inverter. For the
PROFIdrive-compliant interconnection in
the inverter, see also Section: PROFIdrive
profile for PROFIBUS and PROFINET
(Page 120).
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Examples
---
See also Section:
Configuring
PROFIBUS
communication in
STEP 7 (Page 438).
See also Section:
STEP 7 program
examples (Page 447).