Siemens SINAMICS G120 Operating Instructions Manual page 383

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Number
Cause
F30002
DC-link voltage overvoltage
F30003
DC-link voltage undervoltage
F30004
Inverter overtemperature
F30005
I2t inverter overload
F30011
Line phase failure
F30015
Motor cable phase failure
F30021
Ground fault
F30027
Time monitoring for DC link pre-
charging
F30035
Overtemperature, intake air
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
A30049
Internal fan defective
F30059
Internal fan defective
A30502
DC link overvoltage
A30920
Temperature sensor fault
A50001
PROFINET configuration error
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Remedy
If this doesn't help:
U/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit
Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
Check the line voltage (p0210).
Check whether the inverter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
Check the rated currents of the motor and Power Module.
Reduce current limit p0640.
When operating with U/f characteristic: Reduce p1341.
Check the inverter's input fuses.
Check the motor feeder cables.
Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
Check the power cable connections.
Check the motor.
Check the current transformer.
Check the cables and contacts of the brake connection (a wire might
be broken).
Check the supply voltage at the input terminals.
Check the line voltage setting (p0210).
Check whether the fan is running.
Check the fan filter elements.
Check whether the ambient temperature is in the permissible range.
See F30035 and, in addition:
Check the motor load.
Check the line phases
Check the internal fan and if required replace.
Check the internal fan and if required replace.
Check the unit supply voltage (p0210).
Check the dimensioning of the line reactor.
Check that the sensor is connected correctly.
A PROFINET controller is attempting to establish a connection with an
incorrect configuration telegram. Check to see whether "Shared Device"
is activated (p8929 = 2).
Alarms, faults and system messages
11.5 List of alarms and faults
383