5.3

Setting the 50 / 60 Hz selection menu

NOTICE
The 50 / 60 Hz selection menu is visible only on first power-up or after a factory reset
(P0970). You can make a selection using the BOP or exit the menu without making a
selection and the menu will not be displayed unless a factory reset is performed.
The motor base frequency can also be selected by changing P0100 to the desired value.
Functionality
This menu is used to set the motor base frequency according to which region of the world
that the motor is used. The menu determines whether power settings (for example, rated
motor power P0307) are expressed in [kW] or [hp].
Parameter
P0100
50 / 60 Hz selection menu
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
Value
Description
0
Motor base frequency is 50 Hz (default) → Europe [kW]
1
Motor base frequency is 60 Hz → United States / Canada [hp]
2
Motor base frequency is 60 Hz → United States / Canada [kW]
Hz Hz
OK
OK
Setup
Menu
5.3 Setting the 50 / 60 Hz selection menu
Hz Hz
M M
Display
Menu
Commissioning
Hz Hz
37