Backing up data and series commissioning

9.3 Saving settings on an operator panel

9.3
Saving settings on an operator panel
Precondition
When the power supply is switched on, you can transfer the settings
of the inverter to the BOP-2 or, vice versa, transfer the data from the
BOP-2 to the inverter.
Inverter → BOP-2
Procedure
To back up the settings, proceed as follows:
Start data transfer in the menu "EXTRAS" - "TO BOP".
You have backed up the settings.
BOP-2 → inverter
Procedure
To transfer the settings, proceed as follows:
1. Start data transfer in the menu "EXTRAS" - "FROM BOP".
2. Switch off the inverter power supply.
3. Wait until all LED on the inverter go dark. Now switch on the
inverter power supply again. Your settings only become effective
after this power-on reset.
You have transferred the settings.
9.4

Other ways to back up settings

In addition to the default setting, the inverter has an internal memory for backing up three
other settings.
On the memory card, you can back up 99 other settings in addition to the default setting.
You will find additional information on the Internet at: Memory options
(http://support.automation.siemens.com/WW/view/en/43512514).