Siemens SINAMICS G120 Operating Instructions Manual page 228

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Setting functions
8.2 Inverter control
Advanced settings
To change the number of command data sets in STARTER, you must open your STARTER
project offline.
Figure 8-10
,
Parameter
p0010 = 15
p0170
p0010 = 0
r0050
p0809[0]
p0809[1]
p0809[2] = 1
p0810
p0811
r0050
228
Editing command data sets in STARTER
You can edit command data sets if, in the STARTER project tree, you select
"Configuration".
If you require more than two command data sets, then add command data sets using
this button or remove them.
To simplify commissioning several command data sets, under the "Command data
sets" tab there is a copy function.
Description
Drive commissioning: Data sets
Number of command data sets (factory setting: 2)
p0170 = 2, 3 or 4
Drive commissioning: Ready
Displaying the number of the CDS that is currently active
Number of the command data set to be copied (source)
Number of the command data set to which the data is to be copied (target)
Copying is started
Once copying has been completed, the inverter sets p0809[2] to 0.
Command data set selection CDS bit 0
Command data set selection CDS bit 1
Displaying the number of the CDS that is currently active
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents