You have commissioned the automatic restart function.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
The inverter automatically acknowledges faults under the following conditions:
1
p1210 = 1 or 26: Always.
p1210 = 4 or 6: If the command to switch-on the motor is available at a digital input or via the
fieldbus (ON/OFF1 = 1).
p1210 = 14 or 16: Never.
The inverter attempts to automatically switch-on the motor under the following conditions:
2
p1210 = 1: Never.
p1210 = 4, 6, 14, 16, or 26: If the command to switch-on the motor is available at a digital
input or via the fieldbus (ON/OFF1 = 1).
If no fault has occurred one second after flying restart and magnetizing (r0056.4 = 1), the start
3
attempt was successful.
Figure 8-29
Time response of the automatic restart
Setting functions
8.7 Application-specific functions
287