Backing up data and series commissioning
9.1 Saving settings on a memory card
9.1.2
Transferring the setting from the memory card
Automatically transferring
Precondition
The inverter power supply has been switched off.
Procedure
Proceed as follows to automatically transfer your settings:
1. Insert the memory card into the inverter.
2. Then switch on the inverter power
supply.
If there is valid parameter data on the memory card, then the inverter accepts the data from
the memory card.
Manually transferring
Preconditions
• The inverter power supply has been switched on.
• No memory card is inserted in the inverter.
Procedure
Proceed as follows to transfer settings from a memory card using STARTER:
1. Go online with STARTER, and in your drive, select the "Drive Navigator".
2. Select the "Commissioning" button.
3. Select the button to transfer the data from the memory card to the inverter.
4. Select the settings as shown in the diagram and start the data backup.
328
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB