Technical data
12.2 Technical data, Power Modules
Table 12- 19 PM240-2, PT, Frame Sizes C, 3 AC 380 V ... 480 V
Order No. - without filter
Order No. - with filter
LO power
LO input current
LO output current
HO power
HO input current
HO output current
Fuse according to IEC
Fuse according to UL
Power losses without filter
Power losses with filter
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight without filter
Weight with filter
1) 0,08 kW via heat sink;
2) 0,1 kW via heat sink
402
6SL3211...
...1PE23-3UL0
6SL3211...
...1PE23-3AL0
15,0 kW
39,9 A
32,0 A
11,0 kW
36,0 A
26,0 A
3NE 1817-0 (50 A)
50 A Class J
kW
kW
l/s
6 ...16 mm
10 ... 6 AWG
1,3 Nm / 12 lbf in
5,8 kg
6,3 kg
1)
1)
2