Procedure
Proceed as follows to backup your settings on a memory card using STARTER:
1. Go online with STARTER, e.g. via a USB cable.
2. Select the "Commissioning" button.
3. Select the button to transfer the settings to the memory card.
4. Select the settings as shown in the diagram and start the data backup.
5. Close the screen forms.
You have backed up the settings on the memory card using STARTER.
Procedure
Proceed as follows to backup your settings on a memory card using BOP-2:
1. Remove the USB cable if one is inserted in the inverter.
2. Plug a BOP-2 onto the inverter.
3. Go to the menu level "EXTRAS".
4. In the menu, select "EXTRAS" - "TO CRD".
You have backed up the settings on the memory card using BOP-2.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
In STARTER, press the "Copy RAM to ROM" button
In your drive, select "Drive Navigator".
Backing up data and series commissioning
9.1 Saving settings on a memory card
.
327