8.7.3.2

DC braking

DC braking is used for applications without regenerative feedback into the line supply, where
the motor can be more quickly braked by impressing a DC current than along a braking
ramp.
Typical applications for DC braking include:
● Centrifuges
● Saws
● Grinding machines
● Conveyor belts
Function
NOTICE
Motor damage caused by overheating
The motor can overheat if it is braked for long periods of time or frequently using DC
braking. This may damage the motor.
• Monitor the motor temperature.
• If the motor gets too hot during operation you must select another braking method or
With DC braking, the inverter outputs an internal OFF2 command for the time that it takes to
de-energize the motor p0347 - and then impresses the braking current for the duration of the
DC braking.
The DC-braking function is possible only for induction motors.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
give the motor more time to cool down.
DC braking when falling below a start speed
Precondition: p1230 = 1 and p1231 = 14
8.7 Application-specific functions
DC braking when a fault occurs
Precondition: Fault number and fault response
are assigned using p2100 and p2101
Setting functions
269