Siemens SINAMICS G120 Operating Instructions Manual page 109

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Internal interconnection of the analog output
You define the analog output function by interconnecting parameter p0771 with a connector
output of your choice. Parameter p0771 is assigned to the particular analog input via its
index, e.g. parameter p0771[0] is assigned to analog output 0.
Table 6- 5
CO
r0021
r0024
r0025
A complete list of the connector outputs is provided in the List Manual.
For more information, please see the parameter list and the function block diagrams 9572 f
of the List Manual.
Adapting the internal interconnection of the analog output
Example
You wish to output the inverter output current via analog output
0. To do this, you must connect AO 0 with the signal for the
output current.
Procedure
Proceed as follows to interconnect analog output 0 with the signal for the output current
using STARTER:
1. Go online.
2. Select "Inputs/outputs".
3. Change the output function via the corresponding screen form.
You have interconnected analog output 0 with the signal for the output current.
Proceed as follows to interconnect analog output 0 with the signal for the output current
using BOP-2:
1. Go into the menu "PARAMS".
2. As parameter filter, select "EXPERT".
3. Set p0771 = 27
You have interconnected analog output 0 with the signal for the output current.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Connector outputs (CO) of the inverter (selection)
Significance
Actual frequency
Output actual frequency
Output actual frequency
CO
Significance
r0026
Actual DC-link voltage
r0027
Output current
Adapt terminal strip
6.5 Analog outputs
109