Alarms, faults and system messages

11.5 List of alarms and faults

11.5
List of alarms and faults
Axxxxx Alarm
Fyyyyy: Fault
Table 11- 6
The most important alarms and faults of the safety functions
Number
Cause
F01600
STOP A Triggered
F01650
Acceptance test required
F01659
Write task for parameter rejected Cause: The converter should be reset to the factory setting. The resetting of
A01666
Static 1 signal atF-DI for safe
acknowledgment
A01698
Commissioning mode active for
safety functions
A01699
Shutdown path test required
F30600
STOP A Triggered
Table 11- 7
Faults, which can only be acknowledged by switching the converter off and on again (power on reset)
Number
Cause
F01000
Software fault in CU
F01001
Floating Point Exception
F01015
Software fault in CU
F01018
Power-up aborted more than
once
F01040
Parameters must be saved
F01044
Loading of memory data card
defective
F01105
CU: Insufficient memory
F01205
CU: Time slice overflow
F01250
CU hardware fault
F01512
An attempt has been made to
establish an conversion factor
for scaling which is not present
376
Remedy
STO Select and then deselect again.
Carry out acceptance test and create test certificate.
Switch the Control Unit off and then on again.
the safety functions is, however, not allowed, because the safety functions
are currently enabled.
Remedy with operator panel:
p0010 = 30
Parameter reset
p9761 = ...
Enter password for the safety functions.
p0970 = 5
Reset Start Safety Parameter.
The converter sets p0970 = 5 if it has reset the parameters.
Then reset the converter to the factory setting again.
F-DI to a logical 0 signal.
This message is withdrawn after the Safety commissioning has ended.
After the next time that the "STO" function is deselected, the message is
withdrawn and the monitoring time is reset.
STO Select and then deselect again.
Remedy
Replace CU.
Switch CU off and on again.
Upgrade firmware or contact technical support.
After this fault is output, the converter powers up with the factory settings.
Remedy: Back up factory setting with p0971=1. Switch CU off and on again.
Recommission the converter.
Save parameters (p0971).
Switch CU off and on again.
Replace memory card or CU.
Reduce number of data records.
Contact technical support.
Replace CU.
Create scaling or check transfer value.
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB