Technical Data, Pm250 - Siemens SINAMICS G120 Operating Instructions Manual

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

12.2.3

Technical data, PM250

Feature
Line voltage
Output voltage
Input frequency
Power factor λ
Starting current
Pulse frequency (factory
setting)
Electromagnetic
compatibility
Braking methods
Degree of protection
Operating temperature
Storage temperature
Relative humidity
Dirt and contamination
Environmental requirements Protected against damaging chemical substances according to environmental class 3C2 to
Shock and vibration
Installation altitude
Standards
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Version
380 V ... 480 V 3-ph. AC ± 10%
0 V 3-ph. AC ... input voltage x 0.87 (max.)
47 Hz ... 63 Hz
0.9
Less than the input current
4 kHz
The pulse frequency can be increased up to 16 kHz in 2 kHz steps. An increase in the pulse
frequency results in a lower output current.
The devices in compliance with EN 61800-3: 2004 are suitable for Category C1 and C2
environments. For details, see the Hardware Installation Manual, Appendix A2
DC braking, energy recovery (up to 100% of the output power)
IP20 chassis units
LO without derating:
0° C ... +40° C
HO without derating:
0° C ... +50° C
LO/HO with derating:
to 60° C
-40° C ... +70° C
< 95% - condensation not permissible
Protected according to pollution degree 2 to EN 61800-5-1: 2007
EN 60721-3-3; 1995
Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-1:
1997
Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997
Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995
without derating:
up to 1000 m above sea level
with derating:
up to 4000 m above sea level
UL, CE, CE, SEMI F47
The drive only satisfies the UL requirements when UL-certified fuses are used.
Technical data
12.2 Technical data, Power Modules
For details, see the Hardware
Installation Manual.
For details, see the Hardware
Installation Manual
403