Siemens SINAMICS G120 Operating Instructions Manual page 311

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

The inverter monitors the regular forced dormant error detection.
Figure 8-38
Parameter
p9659
r9660
r9773.31
Time of the forced dormant error detection
In the case of warning A01699 , you must initiate a forced dormant error detection at the next
opportunity. These alarms do not affect the operation of your machine.
● Switch off the motor.
● Select function STO or switch off the inverter supply voltage temporarily and on again.
Examples for the times when forced dormant error detection is performed:
● When the drives are at a standstill after the system has been switched on.
● When the protective door is opened.
● At defined intervals (e.g. every 8 hours).
● In automatic mode (time and event dependent).
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Triggering and monitoring the forced dormant error detection
Description
Forced dormant error detection timer (Factory setting: 8 h)
Monitoring time for the forced dormant error detection
Forced dormant error detection remaining time
Displays the remaining time until the forced dormant error detection and testing the
safety switch-off signal paths.
1 signal: Forced dormant error detection is required
Signals for the higher-level control system.
8.8 Safe Torque Off (STO) safety function
Setting functions
311