A.8.4

Go online with STARTER via PROFINET

A.8.4.1

Adapting the PROFINET interface

If you commission the inverter with STARTER via PROFINET, then you must correctly
address your PC and allocate STARTER the interface via which it goes online with the
inverter.
Procedure
To address the inverter, proceed as follows:
1. Establish the bus connection.
2. From the control panel, assign the IP
3. Go to "Start/Settings/Control Panel".
4. Select "Network Connections".
5. Right-click to open the properties window
6. In this window, select "Internet Protocol
7. Select "Properties".
8. Set 192.168.0.100 as the IP address of
9. Open the SIMATIC Manager.
10. Assign the TCP/IP interface to "Intel(R)
You have allocated your computer the IP address and the address of the subnet mask, and
defined the PC interface via which STARTER goes online with the inverter.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
See Section Communication via
PROFINET (Page 112))
address and the subnet mask address to
your computer:
of the LAN connection.
(TCP/IP)".
the supervisor and 255.255.255.0 as
subnet mask.
In the company network it is possible that
the IP address and the subnet mask
have different values. You can obtain
these values from your network
administrator.
PRO/100 VE Network Connection" via
"Tools/PG/PC interface".
Appendix
A.8 Application Examples
445