Siemens SINAMICS G120 Operating Instructions Manual page 367

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Table 11- 4
YELLOW - variable
Table 11- 5
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Communication diagnostics via PROFIBUS DP
LED BF
Explanation
off
Cyclic data exchange (or PROFIBUS not used, p2030 = 0)
RED - slow
Bus fault - configuration fault
RED - fast
Bus fault
- no data exchange
- baud rate search
- no connection
Firmware update in progress
frequency
Diagnostics of the safety functions
SAFE LED
Meaning
YELLOW - on
One or more safety functions are enabled, but not active.
YELLOW - slow
One or more safety functions are active; no safety function faults have
occurred.
YELLOW - rapid
The converter has detected a safety function fault and initiated a STOP
response.
Alarms, faults and system messages
11.1 Operating states indicated on LEDs