Commissioning
4.4 Extended Safety
4.4.2.2

Setting forced dormant error detection and the PROFIsafe address

● Select the values compatible with your application.
– ③ Time interval for forced dormant error detection.
– Further information can be found in the section Forced dormant error detection
● If you only want to use STO, close this screen and go to the section Enabling safety
4.4.2.3

Setting the gear ratio

● If you want to use SS1 or SLS, set the following:
96
– ① This signal triggers a forced dormant error detection and resets the timer.
Interconnect this signal with a binector of your choice, for example a digital input or a
control bit in the field bus.
– ② You must conduct a forced dormant error detection for this signal. Interconnect this
binector with a signal of your choice, for example a digital input or a status bit in the
field bus.
(Page 40).
PROFIsafe address
Enter the same PROFIsafe address as a hexadecimal value, that you defined in the
hardware configuration, see the section Configuring communication in STEP 7 (telegram
30) (Page 64).
functions (Page 97).
If you want to use SS1 or SLS, click this button and go to the next section.
– ① Actual value tolerance:
Leave this set to the factory setting (12.0 °).
– ② ③ Gear ratio:
Enter your machine's data in accordance with the following table.
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA