Siemens SINAMICS G120 Operating Instructions Manual page 387

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Feature
Encoder input
Temperature sensor
Fail-safe digital input
PFH
USB interface
Dimensions (WxHxD)
Weight
Memory cards
Operating temperature
Storage temperature
Relative humidity
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Data
HTL, TTL
500 kHz maximum input frequency
SSI
1 MHz maximum baud rate. The dependency on baud rate and
cable length is shown in the diagram below.
Resolver
The impedances that can be connected and the maximum speed
that can be evaluated are listed below.
PTC
KTY84
Temperature switch isolated contact.
1 (DI 4 and DI 5)
The data of the extended functions of the safety functions can be found in the Safety
Integrated Function Manual, see also Section: Manuals for your converter (Page 461).
5 × 10E-8
Probability of failure of the safety functions (Probability of Failure
per Hour)
Mini-B
73 mm × 199 mm × 63 mm
0.49 kg
Slot for SD or MMC memory cards, also see Section: Overview of Control Units
(Page 24).
0° C ... 50° C
Observe any possible restrictions regarding the operating temperature as a result of the
Power Module.
- 40° C ... 70° C
< 95 %
12.1 Technical data, CU250S-2 Control Unit
Ratio ü = 0.3 ... 0.7
It is always possible to use resolvers with lower or higher ratios.
Ratios ü < 0.3 or ü > 0.7 reduce the accuracy of the speed
sensing and the resolution of the position actual value.
1.8 V
excitation voltage for ü = 0.5
rms
8 kHz excitation frequency, synchronized to the current
controller clock cycle
Short-circuit monitoring 22 Ω
Switching threshold 1650 Ω
Short-circuit monitoring < 50 Ω
Wire break > 2120 Ω
If you have enabled the basic safety functions, DI 4 and DI 5
form the fail-safe digital input.
Maximum input voltage 30 V, 5.5 mA
Response time:
Typical: 5 ms + debounce time p9651
Typical, if debounce time = 0: 6 ms
Worst-case scenario: 15 ms + debounce time
Worst case, if debounce time = 0: 16 ms
The depth specification is valid when mounting on the
Power Module.
Condensation is not permissible.
Technical data
387