Siemens SINAMICS G120 Operating Instructions Manual page 140

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Configuring the fieldbus
7.4 PROFIdrive profile for PROFIBUS and PROFINET
Error
Significance
value 1
6B hex
No change access for a controller that is enabled.
6C hex
Unknown unit.
6E hex
Change request is only possible when the motor is being commissioned (p0010 = 3).
6F hex
Change request is only possible when the power unit is being commissioned (p0010 = 2).
70 hex
Change request is only possible for quick commissioning (basic commissioning) (p0010 = 1).
71 hex
Change request is only possible if the inverter is ready (p0010 = 0).
72 hex
Change request is only possible for a parameter reset (restore to factory setting) (p0010 = 30).
73 hex
Change request possible only during commissioning of the safety functions (p0010 = 95).
74 hex
Change request is only possible when a technological application/unit is being commissioned (p0010 = 5).
75 hex
Change request is only possible in a commissioning state (p0010 ≠ 0).
76 hex
Change request is not possible for internal reasons (p0010 = 29).
77 hex
Change request is not possible at download.
81 hex
Change request is not possible at download.
82 hex
Transfer of the control authority (master) is inhibited by BI: p0806.
83 hex
Desired interconnection is not possible (the connector output does not supply a float value although the
connector input requires a float value)
84 hex
Inverter does not accept a change request (inverter is busy with internal calculations. See parameter r3996 in
the inverter List Manual. See also Section: Manuals for your converter (Page 461))
85 hex
No access methods defined.
86 hex
Write access only during commissioning of the data records (p0010 = 15) (operating status of the inverter
prevents a parameter change.)
87 hex
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit (change request to a value that lies within the "absolute" limits,
but is however below the currently valid lower limit)
C9 hex
Change request above the currently valid limit (example: a parameter value is too large for the inverter power)
CC hex
Change request not permitted (change is not permitted as the access code is not available)
Other application examples
See also: Reading and writing parameters via PROFIBUS
(http://support.automation.siemens.com/WW/view/en/8894584).
140
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB