Setting functions
8.7 Application-specific functions
8.7.7

Load failure monitoring

Load failure
Using this function, the inverter monitors the speed or velocity of a machine component. The
inverter evaluates whether an encoder signal is present. If the encoder signal fails for a time
that can be adjusted, then the inverter signals a fault.
Examples of how the function can be used:
● Gearbox monitoring for traction drives and hoisting gear
● Drive belt monitoring for fans and conveyor belts
● Blocking protection for pumps and conveyor belts
Figure 8-33
Parameter
p2192
p2193 = 1...3
p3232 = 722.x
For more information, see the List Manual (the parameter list and function diagram 8013)
296
Load failure monitoring using a digital input
Description
Load monitoring delay time (factory setting 10 s)
After the motor is switched on, if the "LOW" signal is present at the associated
digital input for longer than this time, the inverter signals a load failure (F07936).
Load monitoring configuration (factory setting: 1)
0: Monitoring is deactivated
1: Torque monitoring (see Monitor the load torque (system protection) (Page 294))
and load failure
2: Speed deviation monitoring (see below) and load failure
3: Load failure monitoring
Load monitoring failure detection (factory setting: 1)
Interconnect the load monitoring with a digital input of your choice.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB