Adapt terminal strip
6.3 Digital outputs
Procedure
Proceed as follows to interconnect digital output DO 1 with the alarm message using
STARTER:
1. Go online.
2. Select "Inputs/outputs".
3. Change the output function via the corresponding screen form.
You have interconnected digital output DO 1 with the alarm message.
Proceed as follows to interconnect digital output DO 1 with the alarm message using BOP-2:
1. Go into the menu "PARAMS".
2. As parameter filter, select "EXPERT".
3. Set p0731 = 52.3
You have interconnected digital output DO 1 with the alarm message.
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, please see the parameter list and the function block diagrams 2230 f
of the List Manual.
Using switchable terminals as digital outputs
In the inverter factory setting, the switchable terminals are active as digital inputs.
Procedure
To use a switchable terminal as digital output proceed as follows:
The switchable terminal is now a digital output.
102
1. Go into the menu
"PARAMS".
2. As a parameter
filter select
"EXPERT".
3. Set the corresponding
bit of parameter
p0728.x to 0.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
1. Go online.
2. In your project, select
the corresponding
inverter.
3. Select "Inputs/outputs".
4. Change the function of
the input via the screen
form "Bidirectional digital
inputs and outputs".