Siemens SINAMICS G120 Operating Instructions Manual page 97

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Changing the function of a digital input
Example
You want to acknowledge inverter fault messages using
digital input DI 1. To do this, you must interconnect DI1
with the command to acknowledge faults (p2103). See the
adjacent diagram.
Procedure
To acknowledge faults with digital input DI 1, using STARTER to establish the
interconnection, proceed as follows:
1. Go online.
2. Select "Inputs/outputs".
3. Change the input function via the corresponding screen form.
You have interconnected digital input DI 1 with the command to acknowledge faults.
To acknowledge faults with digital input DI 1, using BOP-2 to establish the interconnection,
proceed as follows:
1. Go into the menu "PARAMS".
2. As parameter filter, select "EXPERT".
3. Set p2103 = 722.1
You have interconnected digital input DI 1 with the command to acknowledge faults.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Adapt terminal strip
6.1 Digital inputs
97