8.2.6

Three-wire control, method 1

With one control command, you enable the two other control commands. You switch the
motor off by withdrawing the enable (OFF1).
You switch the motor's direction of rotation to clockwise rotation with the positive edge of the
second control command. If the motor is still switched off, switch it on (ON).
You switch the motor's direction of rotation to counter-clockwise rotation with the positive
edge of the third control command. If the motor is still switched off, switch it on (ON).
Figure 8-6
Table 8- 5
Parameter
p0015 = 19
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
p3330[0 ... n] = 722.x
p3331[0 ... n] = 722.x
p3332[0 ... n] = 722.x
Example
p3332 = 722.0
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Three-wire control, method 1
Function table
Enable / OFF1
ON clockwise
0
1
1
1
Description
Macro drive unit
Controlling the motor using
the digital inputs of the
inverter:
BI: 2-3-WIRE control command 1 (enable/ OFF1)
BI: 2-3-WIRE control command 2 (ON clockwise rotation)
BI: 2-3-WIRE control command 3 (ON counter-clockwise rotation)
DI 0: ON counter-clockwise rotation.
Also see section Digital inputs (Page 96).
ON clockwise
rotation
rotation
0 or 1
0 or 1
0→1
0
0
0→1
1
1
Function
OFF1: The motor stops.
ON: Clockwise motor rotation.
ON: Counter-clockwise motor
rotation.
OFF1: The motor stops.
DI 0
DI 1
Enable /
ON clockwise
OFF1
rotation