Signal Interconnection Of The Telegram - Siemens SINAMICS G120 Operating Instructions Manual

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Parameter
p0922
p2079
r2050[0...11]
p2051[0...13] PROFIdrive PZD send word
Selection of the PZD (actual values) in the word format to be sent to the PROFIdrive
controller. For further information refer to the function block diagrams 2468 and 2470 of the
List Manual.
Freely selecting the signal interconnection of the telegram
The signals in the telegram can be freely interconnected.
Procedure
Proceed as follows to change the signal interconnection of a telegram:
1. Using STARTER or an operator panel, set parameter p0922 = 999.
2. Using STARTER or an operator panel, set parameter p2079 = 999.
3. Interconnect additional PZD send words and PZD receive words with signals of your
You have freely interconnected the signals transferred in the telegram.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Description
PROFIdrive telegram selection
999:
Free telegram (message frame) configuration
PROFIdrive PZD telegram selection extended
The following values apply if you have still not enabled the "Basic positioner" function
in the inverter:
1:
Standard telegram 1, PZD-2/2
2:
Standard telegram 2, PZD-4/4
3:
Standard telegram 3, PZD-5/9
4:
Standard telegram 4, PZD-6/14
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352:
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, PKW-4/4
The following values apply if you have enabled the "Basic positioner" function in the
inverter:
7:
Standard telegram 7, PZD-2/2
9:
Standard telegram 9, PZD-10/5
110:
SIEMENS telegram 110, PZD-12/7
111:
SIEMENS telegram 111, PZD-12/12
PROFIdrive PZD receive word
Connector output to interconnect the PZD (setpoints) in the word format received
from the PROFIdrive controller.
Selection of the PZD (actual values) in the word format to be sent to the PROFIdrive
controller.
choice via parameters r2050 and p2051.