Communication via PROFIBUS and PROFINET
3.5 Communication via PROFIBUS
3.5.5

Setting the address

Valid address range: 1 ... 125
The position of the address switch is described in the operating instructions of the inverter.
Procedure
To change the bus address, proceed as follows:
1. Set the address using one of the subsequently listed options:
– using the address switch
– from an operator panel using parameter p0918
– in STARTER using screen form "Control Unit/Communication/PROFIBUS" – or using
2. Switch off the inverter supply voltage.
3. Wait until all LEDs on the inverter go dark.
4. Switch on the inverter supply voltage again.
Your settings become active after switching on.
You have now changed the bus address.
74
the expert list in parameter p0918
After you have changed the address in STARTER, carry out RAM to ROM (
You set the PROFIBUS address of the inverter using
the address switch on the Control Unit, in parameter
p0918 or in STARTER.
In parameter p0918 (factory setting: 126) or in
STARTER, you can only set the address, if all
address switches are set to "OFF" (0) or "ON" (1).
If you have specified a valid address with the
address switches, this address will always be the
one that takes effect and parameter p0918 cannot
be changed.