Analog Outputs - Siemens SINAMICS G120 Operating Instructions Manual

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6.5

Analog outputs

Analog output terminals
Define the analog output type
The converter offers a series of default settings, which you can select using parameter
p0776:
AO 0
AO 1
Characteristics of the analog output
If you change the analog output type, then the inverter automatically selects the appropriate
scaling of the analog output. The linear scaling characteristic is defined using two points
(p0777, p0778) and (p0779, p0780).
Figure 6-5
Parameters p0777 ... p0780 are assigned to an analog output via their index, e.g.
parameters p0777[0] ... p0770[0] belong to analog output 0.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
Current output (factory setting)
Voltage output
Current output
Current output (factory setting)
Voltage output
Current output
Examples for scaling characteristics
Changing the function of the analog output
1. Define the analog output type using parameter
p0776 (e.g. voltage output -10 V ... 10 V or
current output 4 mA ... 20 mA).
2. Interconnect parameter p0771 with a
connector output of your choice (e.g. the
actual speed).
In the parameter list of the List Manual,
connector outputs are marked with "CO".
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
Adapt terminal strip
6.5 Analog outputs
p0776[0] =
0
1
2
p0776[1] =
0
1
2
107