Switching over the inverter control (command data set)

In several applications, the inverter must be able to be operated from different, higher-level
control systems.
Example: You control the motor either from a central control system, via fieldbus or from a
local control panel.
Command data set (CDS)
This means that you can set the inverter
control in various ways and toggle between
the settings. For instance, as described
above, the inverter can either be operated
via a fieldbus or via the terminal strip.
The settings in the inverter, which are
associated with a certain control type of the
inverter, are called command data set.
226
Description
Jogging 1 speed setpoint (factory setting 150 rpm)
Jogging 2 speed setpoint (factory setting -150 rpm)
Maximum speed (factory setting 1500 rpm)
Inhibit negative direction
=0: Negative direction of rotation is enabled =1: Negative direction of rotation is
Inhibit positive direction
=0: Positive direction of rotation is enabled
Setpoint inversion
=0: Setpoint is not inverted
Ramp-function generator ramp-up time (factory setting 10 s)
Ramp-function generator ramp-down time (factory setting 10 s)
Jog bit 0: Select jogging 1 via digital input 0
Jog bit 1: Select jogging 2 via digital input 1
inhibited
=1: Positive direction of rotation is
inhibited
=1: Setpoint is inverted
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB