Installation
4.4 Connecting the inverter to PROFIBUS
You have now connected the inverter to the control system using PROFIBUS DP.
4.4.3

Installing the GSD

Procedure
1. Save the GSD on your PC via one of the following methods.
– With Internet access:
– Without Internet access:
2. Unzip the GSD file on your computer.
3. Import the GSD in the engineering system of the controller.
You have now installed the GSD file in the engineering system of the controller.
4.4.4

Setting the address

Valid address area: 1 ... 125
You have the following options for setting the address:
● Using the address switch on the Control Unit:
Figure 4-20
The address switch has priority over the other settings.
● Using Startdrive or an operator panel via parameter p0918 (default setting: p0918 = 126)
It is only possible to change p0918 if an invalid address is set in the address switch.
78
GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100)
Insert a memory card into the inverter.
Set p0804 to 12.
The inverter writes the GSD as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
Address switch with example for bus address 10
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF