Installing
4.3 Installing the Power Module
Dimensions and drilling patterns for Power Modules with through-hole technology
Table 4- 9
Frame
size
FSA
FSB
FSC
1)
2)
3)
Table 4- 10
Frame size
FSA ... FSC
48
Mounting cutout in the control cabinet for PM240-2 Power Modules;
Dimensions and clearances for PM240-2 in through-hole technology, FSA ... FSC
Height
Width Depth
1)
238
126
345
154
411
200
With shield connection kit: FSA: +84 mm; FSB: +85 mm; FSC: +89 mm
You can mount the mounting frames without any lateral clearance. For tolerance reasons, we
recommend a lateral clearance of approx. 1 mm.
Total depth of the inverter: See below.
Mounting materials for PM240-2 in through-hole technology
Material
M5 screws
Holes to mount the mounting frame
FSA, FSB
Dimensions (mm)
T1
T2
a
171
118
54
103
171
118
54
147,5 134 116 304 34,5
171
118
54
123
Tightening torque
3 Nm
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
FSC
b
c
d
e
Top Bottom Lateral
106
88
198
27
174 156 365 30,5
Converter with the CU250S-2 Control Unit (vector)
Clearances (mm)
80
100
0
2)
80
100
0
2)
80
100
0
2)

Hide quick links: