CANopen Mode
Object 6098h: Homing method
Index
12
Name
Object code
Data type
Access
PDO mapping
Setting range
Default
Object function:
The homing methods include looking for the Z pulse (Methods 1 - 14, 33, 34, 36, 37), not
looking for the Z pulse (Methods 17 - 30), defining the current position as the origin (Method
35), and looking for the hard stop (Methods 36 - 39). Methods 15, 16, 31, and 32 are reserved.
To use Methods 1 to 35, set OD 6098h to 1 to 35. To use Methods 36 to 39, set OD 6098h to
-1 to -4.
Method 1: homing on the negative limit switch and Z pulse
Negative limit
Method 2: homing on the positive limit switch and Z pulse
Positive limit
12-76
6098h
Homing method
VAR
INTEGER8
RW
Yes
-4 to 35
0
indicates OD 6099h sub1 1
indicates OD 6099h sub2 2
Z pulse
switch
Starting point
Z pulse
switch
st
homing speed
nd
homing speed
2
ASDA-A3
Starting
point
1