Troubleshooting
ALF22 Password does not match
Trigger condition
14
and cause
Checking method
and corrective action
How to clear the
alarm?
14-90
Condition: the password of the second development platform project does not
match that of the servo drive.
Cause: the password of the second development platform project does not match
that of the servo drive.
Check if the password of the second development platform and the password of
the servo drive are input correctly.
You can change the password of the second development platform project
1.
with the EzASD software, but you cannot reset the password.
You can change the servo drive password with the EzASD software.
2.
You can also set P2.008 to 10 to reset the servo drive password.
Note that setting P2.008 to 10 not only resets all parameters but also clears
the second development platform projects stored in the servo drive.