Delta ASDA-A3 Series User Manual page 648

Hide thumbs Also See for ASDA-A3 Series:
Table of Contents

Advertisement

ASDA-A3
P1.053
Determined by the model. Refer to
Default:
the following table.
Unit: Watt
Format: DEC
Settings:
Setting the parameter value when connecting the regenerative resistor with different methods:
Regenerative resistor capacity
Model
200 W or below
400 W - 1.5 kW
2 kW - 3 kW
220V
4.5 kW
5.5 kW - 7.5 kW
11 kW - 15 kW
1.5 kW or below
400V
2 kW - 15 kW
External regenerative resistor
Exte rnal rege nerative
resistor (para llel)
P3
1 kW, 10 Ω
1 kW, 10 Ω
C
Control mode: All
Setting range: 0 to 15000
Data size: 16-bit
Default (Watt)
0
40
80
60
0
0
60
0
Setting
Setting:
P1.052 = 10 (Ω)
P1.053 = 1000 (W)
Setting:
P1.052 = 20 (Ω)
P1.053 = 2000 (W)
Setting:
P1.052 = 5 (Ω)
P1.053 = 2000 (W)
Parameters
Address: 016AH
016BH
8
8-71