Mitsubishi Electric MELDAS 60 Series Parameter Manual page 343

Cnc
Hide thumbs Also See for MELDAS 60 Series:

Advertisement

No.
Items
3255
SP055 SETM
(PR)
3256 SP056 PYVR
3257
SP057 STOD
(PR)
3258
SP058 SDT2
(PR)
3259
SP059 MKT
(PR)
3260
SP060 MKT2
(PR)
3261
SP061 MKIL
(PR)
3262 SP062
8. Spindle Parameters
8.3 MDS-B-SP/SPH, MDS-C1-SP/SPH
Excessive
Set the timer value until the excessive speed
speed
deviation alarm is output.
deviation
The value of this parameter should be longer
timer
than the acceleration/deceleration time.
Variable
Set the minimum value of the variable
excitation
excitation rate.
(min value)
Select a smaller value when gear noise is too
high. However, a larger value is effective for
impact response.
Constant →
Set the value for judging when changing from a
constant to excessive speed command.
excessive
judgment
value
Fixed
Set by Mitsubishi.
control
Set "0" unless designated in particular.
constant
Winding
Set the base shut-off time for contactor
changeover
switching at winding changeover.
base
Note that the contactor may be damaged with
shut-off
burning if the value of this parameter is too
timer
small.
Current limit
Set the current limit time to be taken after
timer after
completion of contactor switching at winding
winding
changeover.
changeover
Current limit
Set the current limit value during a period
value after
defined in SP060 (MKT2) after completion of
winding
contactor switching at winding changeover.
changeover
Not used. Set to "0".
Details
II - 247
Setting
Standard
range
setting
0 to 60 (s)
12
0 to 100
50
(%)
0 to 50
0
(r/min)
0
0
50 to
150
10000
(ms)
0 to 10000
500
(ms)
0 to 120
75
(%)
0
0