Siemens Simovert Masterdrives Compendium page 93

Motion control
Hide thumbs Also See for Simovert Masterdrives:
Table of Contents

Advertisement

Instructions for Design of Drives in Conformance with EMC Regulations
Radio interference
suppression filter
L1
L2
TN supply
or
TT supply
L3
PE
3-6
Line filter
Frequency converter
Z
N
Z
E
Fig. 3-3
Flow of the noise current with shielded motor cable
A shielded motor cable with a shield connected at both sides causes
the noise current to flow back to the frequency converter through the
shield.
Although (almost) no voltage drop arises across impedance Z
shielded motor cables, the voltage drop across impedance Z
affect other electrical units.
For this reason, a radio interference suppression filter should be
installed in the supply feeder cable to the frequency converter.
Arrangement of the components as per the following figure.
Line reactor
1U1
1U2
L1'
1V1
1V2
L2'
1W1
1W2
L3'
PE'
Mounting panel
Fig. 3-4
Arrangement of the components
Radio interference suppression filters and frequency converters must
be connected through a low-ohmic resistance for the high-frequency
noise currents. In practice, this requirement is best satisfied by
mounting the frequency converters and radio interference suppression
filters on a common panel. Frequency converters and radio interference
suppression filters must be connected to the mounting panel through
the largest possible surface area.
The SIMOVERT MASTERDRIVES must be installed in an enclosed
cabinet in order to limit the radio interference radiation. In particular,
the radio interference radiation is determined by the control section with
its microprocessor and it is therefore comparable with the noise emitted
from a computer. If there are no radio transmission services in the
immediate vicinity of the SIMOVERT MASTERDRIVES, there is no
need for a high-frequency-sealed cabinet.
Radio interference radiation is not limited if the units are installed in
racks. In this case, adequate shielding should be provided by suitably
designing the equipment room/area.
Shielded motor supply cable
SIMOVERT
MASTERDRIVES
U1
U2
V1
V2
W2
W1
PE2
PE1
6SE7087-6QX70 (Version AD)
Compendium Motion Control
05.2003
M
3 ~
I
S
for
E
can
N
Shielded motor
cable
M
3~
Siemens AG
SIMOVERT MASTERDRIVES

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents