Parameterizing Steps
P060 = 8
P070 = ?
P060 = 1
NOTE
6-6
The unit has to be switched to the "Power section definition" state for
carrying out the power section definition. This is done by selecting the
"Power section definition" menu. The power section is then defined in
this menu by inputting a code number.
Select "Power section definition" menu
Input the code number for the unit concerned
The code number is allocated to the order numbers (MLFB).
The order number can be read off the unit's rating plate.
The list of units is on the following pages.
Return to parameter menu
Fig. 6-3
Sequence for performing the power section definition
To check the input data, the values for the converter supply voltage in
P071 and the converter current in P072 should be checked after
returning to the parameter menu. They must tally with the data given on
the unit rating plate.