Engineering Information
Notes regarding the
use of a power back-
up module
Notes on pulse
frequency
11-24
The power back-up module is for increasing the capacity of the DC link.
This can bridge a short-time power-system failure, on the one hand,
and also enables intermediate storage of braking energy, on the other.
♦ Storage capacity in the event of a power failure:
1
2
=
⋅ ⋅
W
C U
(
Link n
2
With a 400 V supply voltage and when C = 5.1 mF and
U
= 400 V, for example, the storage capacity is calculated as
Link min
follows:
1
3
=
W
5 1 10
.
(( .
135 400
2
With a 460 V supply voltage, the storage capacity increases to
575 W. The possible bridging time t
power P as follows:
W
=
t
bri
P
The storage capacity during regenerative operation is calculated as
follows:
1
2
=
⋅ ⋅
W
C U
(
Link
max
2
With a 400 V supply voltage and when U
1
3
=
W
5 1 10
.
(
750
2
During braking, for example, from maximum speed to 0 within time t
the braking energy is calculated as follows:
1
=
W
P
t
br
br
max
2
with maximum motor braking power in W
M
Mot v
max
=
P
br
max
9 55
M
Maximum motor torque during braking in Nm
Mot v max
Maximum motor speed during braking in rpm
n
Mot max
♦ Maximum number of power back-up modules which can be
connected on a Compact PLUS unit is
• Two power back-up modules for rectifier units
• One power back-up module for converters
The level of the pulse frequency basically affects the dynamic
response. Accordingly, when a high level of dynamic response is
required, the pulse frequency should be set to 10 kHz. Use of the
Compact PLUS does not therefore entail derating. Compact units and
chassis-type units require derating of 6 or 3 Hz and upwards,
depending on their power output (see technical data). A reduction of the
permissible rated current entails a reduction of the permissible
maximum current to the same amount. In addition, the maximum pulse
frequency with chassis-type units is lower than 10 kHz (see technical
data).
2
U
)
Link
min
2
2
=
)
400
)
336
is calculated with the output
bri
2
U
)
Link n
2
2
− −
=
(
1 35 400
) )
v
n
Mot
max
η
η
Mot
Inv
.
6SE7087-6QX70 (Version AE)
Compendium Motion Control
06.2005
Ws
=750 V:
Link max
691
Ws
Siemens AG
SIMOVERT MASTERDRIVES