Src1 OFF2(coast)
P555.B (1/20)
B
Src2 OFF2(coast)
P556.B (1/1)
B
Src3 OFF2(coast)
P557.B (1/1)
B
"Safe STOP" check-back 3)
Src1 OFF3(QStop)
P558.B (1/1)
B
Src2 OFF3(QStop)
P559.B (1/1)
B
Src3 OFF3(QStop)
P560.B (1/1)
B
Src1 Fault Reset
P565.B(2107)
B
Src2 Fault Reset
P566.B (0/0)
B
Src3 Fault Reset
P567.B (0/18)
B
Pulse generator
from PMU [50.7]
The sequence control system is the
1)
internal control system (software) for
implementing the drive status (r001).
2)
The signal remains high on acknowledgement at least
for T10 (= 204.8 ms with 5 kHz pulse frequency).
Pre-assignment of the BICO parameters:
1. Binector valid for BICO data set 1
2. Binector valid for BICO data set 2
3)
For Compact PLUS devices from function
diagram 91.4 or 92.4: Only evaluated in the
"Ready for switching on" state (r001 = 9) with
compact and chassis devices.
1
2
Control word 1
Bit No.
Src ON/OFF1
P554.B (0/0)
B
Bit 0
Bit 1
Bit 2
Src InvRelease
P561.B (1/1)
B
Bit 3
Src RampGen Rel
P562.B (1/1)
B
Bit 4
Src RampGen Stop
P563.B (1/1)
B
Bit 5
Src Setp Release
P564.B (1/1)
B
Bit 6
Bit 7
Src Jog Bit0
P568.B (0/0)
B
Bit 8
Src Jog Bit1
P569.B (0/0)
B
Bit 9
Bit 10
Src FWD Speed
P571.B (1/1)
B
Bit 11
Src REV speed
P572.B (1/1)
B
Bit 12
Src MOP UP
P573.B (0/0)
B
Bit 13
Src MOP Down
P574.B (0/0)
B
Bit 14
Src No ExtFault1
P575.B (1/1)
B
Bit 15
3
4
Meaning
0=OFF1,Shutdown via ramp-function generator, followed
by pulse disable
1=ON, operating conditions (edge-controlled)
0=OFF2,Pulse disable, motor coasts down
1=Operating condition
0=OFF3, Quick stop
1=Operating condition
1=Inverter enable, pulse enable
0=Pulse disable
1=Ramp-function-generator enable
0=Set ramp-function generator to 0
1=Start ramp-function generator
0=Stop ramp-function generator
1=Setpoint enable
0=Setpoint disable
0 => 1 Edge fault acknowledgement
1=Inching bit 0
1=Inching bit 1
1=Control requested
0=No control requested
1=Clockwise phase sequence enable
0=Clockwise phase sequence disable
1=Counter-clockwise phase sequence enable
0=Counter-clockwise phase sequence disable
1=Raise mot. potentiometer
1=Lower mot. potentiometer
0=External fault 1 (F035),
1=No external fault
5
6
V2.5
fp_mc_180_e.vsd
10.02.03
n959.25 = 4
Display of r550 on the PMU
Control word 1
15 14
13 12
11 10
r550
Control word 1
K0030
7
6
5
4
3
to sequence control 1)
to sequence control 1)
to sequence control 1)
to sequence control 1)
to sequence control 1)
to setpoint processing (part 2) [320.2]
to setpoint processing (part 2) [320.2]
B0094
Fault acknowl. 2)
to sequence control 1)
to sequence control 1)
to sequence control 1)
Note: This bit must be set in the first PcD word of the
telegram received from the serial interfaces so that the
converter will accept the process data as valid (compare
USS, Profibus etc.; does not apply to SIMOLINK)
to setpoint processing (part 1) [310.7]
to setpoint processing (part 1) [310.7]
to mot. potentiometer [300.2]
to mot. potentiometer [300.2]
to sequence control 1)
to fault processing
7
8
Function diagram
MASTERDRIVES MC
9
8
2
1
0
- 180 -