2.4.7.1
Protective door safety function
Assumption
Siemens AG
6SE7087-6QX70 (Version AM)
SIMOVERT MASTERDRIVES
When the protective door is opened, the drive must be brought to a
safe standstill and switched off after a safely monitored timer has run
down.
The protective door is opened every 10 minutes in two-shift operation.
The working period is Monday to Friday.
The actuations are calculated to be 6 x 1/h *16 h/d *260d = 24960 per
year.
Fig. 2-16
Block diagram of the protective door safety function
The safety switching device –A1 is required to diagnose –K2 and –K3.
It is not included in the calculation for the protective door safety
function.
Compendium Motion Control
Configuration and Connection Examples
2-45