09.2008
No.
Cause
No. 0 .. 199: S7 task has been changed into a parameter task. Fault detection in the basic board
or technology board. Additional info in r732.23, r732.24: parameter number, index word.
0
There is no parameter number
1
Parameter value cannot be altered
2
Top or bottom limit exceeded
3
There is no subindex
4
Access to single value with array identifier
5
Access to word with double word task or vice
versa
6
Setting not allowed (can only be reset)
7
Description element cannot be altered
11
No parameter change rights
12
Keyword missing
15
There is no text array
17
Task cannot be executed due to operating
status
101
Parameter number deactivated at the moment
102
Channel width too small
103
PKW number incorrect
104
Parameter value not permissible
105
Access to array parameter with single identifier
106
Task not implemented
No. 200-209: S7 task is formally defective. Error detection in the COM BOARD.
Additional info in r732.23, r732.24: data block number, data block offset
200
Error in variables address (no addiional info)
201
Data block number not permissible
202
Data block offset not permissible
203
Non-permissible "Type" during access to
parameter value
204
Non-permissible "Number of elements" during
access to parameter value
205
Non-permissible "Type" during access to text
206
Non-permissible "Type" during access to
description
207
Non-permissible odd "Number of elements" in
the case of type CHAR or BYTE
208
Non-permissible change of text/description
209
Inconsistency in the write task: "Type" and
"Number of elements" does not match "Type of
data" and "Length of data"
Siemens AG
6SE7087-6QX70 (Version AK)
SIMOVERT MASTERDRIVES
Fault S7 protocol (r732.22), fault numbers < 150 correspond to PKW fault
numbers:
Compendium Motion Control
Communication / PROFIBUS
Remedy (e.g. in ProTool)
Check data block number
-
-
Check data block offset
Set data block offset = 0
Use correct type of data
(e.g. INT for word, DINT for double word)
-
(should not occur here)
-
-
-
-
-
(should not occur here)
(should not occur here)
-
Set data block offset > 0
-
Permissible: range of "Data block"
Permissible: 1...31999
Permissible:
0...116, 10001...10116, 20000...20010
Permissible: CHAR. BYTE, INT, WORD, DINT,
DWORD, REAL
Permissible: effective 2 or 4 byte
Permissible: CHAR, BYTE
Permissible: CHAR. BYTE, INT, WORD, DINT,
DWORD, REAL
Correct the "Number of elements"
-
(Defective communications partner)
8.2-135