Siemens Simovert Masterdrives Compendium page 329

Motion control
Hide thumbs Also See for Simovert Masterdrives:
Table of Contents

Advertisement

Communication / USS
"Interconnection" of
status words 1 and 2
and the actual
values
NOTE
Example 1
Parameter
Parameter
No.
P707
SCom1 actual
values
8.1-42
The two status words 1 (bits 0 to 15) and 2 (bits 16 to 31) send
messages from the converter to a higher-level converter system.
An indexed parameter is assigned to each interface. Each index is
assigned to a net-data word in the PZD area. For example, index i001
to the 1st word, index i002 to the 2nd word and so on up to i016.
Parameter
number
SCom1
SCom2
(not with the
Compact PLUS)
SCB2
706 (SCB actual values)
Status word 1 is always transferred in the 1st word of the PZD area in
the USS protocol.
"Interconnection" of status word 1 and the actual speed/frequency
(KK0091) at interface SCom1.
♦ Precondition:
PZD area at least 2 words in length; P703, i001 ≥ 2 is set.
Index and value
i001 = 0032
i002 = 0091
i003 to i016 = 0
Parameter
707 (SCom1 actual
values)
708 (SCom2 actual
values)
Comments
1st word in the PZD area:
status word (K0032)
2nd word in the PZD area:
actual speed/frequency (KK0091, only H-Word)
3rd to 16th word in the PZD area (if parameterized):
"Not interconnected"
6SE7087-6QX70 (Version AD)
Compendium Motion Control
02.2004
Index and value
(index i001 for BICO data set 1)
(index i002 for BICO data set 2)
i001 to 016
i001 to 016
i001 to 016
Siemens AG
SIMOVERT MASTERDRIVES