Instructions for Design of Drives in Conformance with EMC Regulations
3-20
Fig. 3-15
Installing the motor connection and the connecting adapter
The following procedure should be carried out to connect the motor
cable and to mount the shield:
♦ First connect the motor cable to the removed X2 motor connector
♦ Connect the shield of the motor cable through the largest possible
surface area at the connecting adapter, e.g. with shield clamps.
♦ Insert the fastening straps of the connecting adapter through the
slots in the lower housing section and screw them into place.
♦ Locate the motor connector X2 and screw tightly to the unit.
The control cables can be attached at the front of the connecting
adapter using shield clamps.
6SE7087-6QX70 (Version AD)
Compendium Motion Control
05.2003
Connecting
adapter
Shield
clamp